C-Bus Passive Infrared Occupancy Detector 90 Degrees

Home ProductsSmart HomeC-BusPassive Infrared Occupancy Detector

C-Bus Passive Infrared Occupancy Detector 90 Degrees | White Electric

Item Number: 5751L-WE

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

C-Bus

Range

C-Bus

Product brand

Clipsal

Product or component type

occupancy sensor

Device application

lighting

Sustainable offer status

Green Premium product

Physical

Sensor type

PIR

Protection type

creep zone protection

Type of setting

light sensitivity adjustable

Number of channels

1

Movement detection area

6 m

Device mounting

surface

Mounting height

2.4 m

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant with Exemptions

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP121002EN

Circularity profile

ENVEOLI121002EN

Material

Material

plastic

Others

Package 1 bare product quantity

1

Product specific application

staircase monitoring

Detection face

lateral: 6 m|frontal: 8.5 m

Horizontal detection angle

0...120 °

Vertical detection angle

90 °

Time delay range

0...1 s (switch-on)

Duty cycle

1080 min

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

7.8 cm

Package 1 width

12.0 cm

Package 1 length

11.7 cm

Package 1 weight

180.0 g

Unit type of package 2

CAR

Number of units in package 2

20

Package 2 height

30.0 cm

Package 2 width

30.0 cm

Package 2 length

40.0 cm

Package 2 weight

4.9 kg

Unit type of package 3

PAL

Number of units in package 3

320

Package 3 height

120.0 cm

Package 3 width

60.0 cm

Package 3 length

80.0 cm

Package 3 weight

88.4 kg

Weee

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • Technical Data Catalogues

  • End of Life Manual

  • Environmental Disclosure

  • Operating Manuals

  • Declaration of Conformity

  • Software - Release

Frequently Asked Questions

hide show

How to Program "Absence Detection" on C-Bus outdoor PIR sensor?

Objective:
Absence detection sets the sensor to detect the absence of motion. If the lighting is on and the sensor detects the absence of motion, a timer is activated. When the timer expires and the sensor element still detects absence, a C-Bus command is sent to control lighting.
This article will guide you how to program “Absence Detection”, it will cover those C-Bus sensors, 5751L, 5750WPL and 5753L with the old firmware v1.2.67.

Product Line:
C-Bus Sensors: 5751L, 5750WPL and 5753L with the old firmware v1.2.67

Environment:
C-Bus Toolkit 1.15.5

Resolution:
  1. Open C-Bus Toolkit
  2. Scan the Network
  3. Double click the sensor to open its GUI
  4. Select a control group from the “Key 1 Group” dropdown list
  5. Define the Expiry Time (5 minutes assigned by default) and click “OK”
  6. Go to Key Functions tab and change the “On Key” on MD column for Short Press to “Idle”
  7. A Confirm-21000 message will pop up
  8. Click “YES” to accept the non-PIR functions
  9. Click “Apply” or “OK”
  10. Save to Database and Physical Unit