Can Compact NSX communicate with motor mechanism installed?

FAQ000208900

30 September 2021

Standard Compact NSX motor mechanism doesn't have the option for communication. 

 

You would require a communicating Motor mechanism + BSCM + NSX Cord in order to achieve this. 

NSX Motor mechanism

Please note: communicating Motor mechanism only comes in 220-240VAC. 

 

NSX 100/160/250

NSX 400/630

 

You would also require IFM (LV434000) for Modbus output or IFE (LV434001 or LV434002) for Modbus TCP/IP, Ethernet. 

 

Once you have the above units/modules, then you should be able to control your circuit breaker with communication such as PLC. 

 

List of Modbus registers can be found from Compact NSX communication guide 

https://www.se.com/au/en/download/document/DOCA0091EN/

 

Attached is wiring diagram of NSX Motor Mechanism.
 

;