Can Compact NSX communicate with motor mechanism installed?
FAQ000208900
30 September 2021
Standard Compact NSX motor mechanism doesn't have the option for communication.
You would require a communicating Motor mechanism + BSCM + NSX Cord in order to achieve this.
Please note: communicating Motor mechanism only comes in 220-240VAC.
NSX 100/160/250
NSX 400/630
You would also require IFM (LV434000) for Modbus output or IFE (LV434001 or LV434002) for Modbus TCP/IP, Ethernet.
Once you have the above units/modules, then you should be able to control your circuit breaker with communication such as PLC.
List of Modbus registers can be found from Compact NSX communication guide
https://www.se.com/au/en/download/document/DOCA0091EN/
Attached is wiring diagram of NSX Motor Mechanism.