Frequently asked questions
Video: How do I program and wire an ATV212 to run using 3-wire control?
FA274408
21 July 2022
Issue:Configuring Altivar 212 Drives for 3-Wire Control
Product Line:
Altivar 212, Altivar
Environment:
All
Cause:
Need to use 3-wire (momentary) control
Resolution:
Programming:
Press MODE key to AUF
Arrow down to F---, and press ENT key
Set F111 to 2
Set F112 to 49
Wiring:
Wire the F terminal from a Normally Open (NO), momentary close, START contact
Wire the R terminal from a Normally Closed (NC), momentary open, STOP contact