Resi9 Residual current circuit breaker (RCCB) 2P, 40A, A type, 30mA

Home ProductsCircuit ProtectionResi9Residual current circuit breaker (RCCB)

Resi9 Residual current circuit breaker (RCCB) 2P, 40A, A type, 30mA

Item Number: R9R06240

Datasheet

Product Dimensions

Width icon

Width36 mm

Height icon

Height85 mm

Depth icon

Depth75 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Resi9

Product or component type

residual current circuit breaker (RCCB)

Sustainable offer status

Green Premium product

Physical

[in] rated current

40 A conforming to AS/NZS 61008.1

[ue] rated operational voltage

400 V

Control type

toggle

Local signalling

ON/OFF indication

Mounting mode

clip-on

Mounting support

DIN rail

Height

85 mm

Width

36 mm

Depth

75 mm

Net weight

210 g

Mechanical durability

10000 cycles

Electrical durability

4000 cycles AC 50 Hz

Connections - terminals

tunnel type terminals (top or bottom)

Wire stripping length

14 mm for top or bottom connection

Standards

IEC 61008-2-1|EN/IEC 61008-1

Ip degree of protection

IP20

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-25...70 °C

Ambient air temperature for storage

-40...85 °C

Reach regulation

Reference contains Substances of Very High Concern above the threshold

Eu rohs directive

Compliant with Exemptions

Mercury free

Yes

Rohs exemption information

Yes

China rohs regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental disclosure

ENVPEP2210006EN

Circularity profile

ENVEOLI2210006EN

Others

Commercial status history

SESA65410 | Mon Sep 25 00:14:00 EDT 2023 | From Import Local | From 02 to 08

Package 1 bare product quantity

1

Poles description

2P

Network type

AC

Earth-leakage sensitivity

30 mA

Earth-leakage protection time delay

instantaneous

Earth-leakage protection class

type A

Rated breaking and making capacity

Im 500 A at 400 V AC 50 Hz conforming to AS/NZS 61008.1

Rated conditional short-circuit current

Resi9 MCB: Inc 6 kA 40 A

Quality labels

RCM

Network frequency

50 Hz

[ui] rated insulation voltage

440 V AC 50 Hz conforming to AS/NZS 61008.1

[uimp] rated impulse withstand voltage

4 kV

Surge current

250 A

9 mm pitches

4

Tightening torque

3.5...3.5 N.m top or bottom

Pollution degree

2

Overvoltage category

III

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

8 cm

Package 1 width

9 cm

Package 1 length

4 cm

Package 1 weight

0.214 kg

Unit type of package 2

BB1

Number of units in package 2

6

Package 2 height

9 cm

Package 2 width

25.4 cm

Package 2 length

10.6 cm

Package 2 weight

1.386 kg

Unit type of package 3

S03

Number of units in package 3

54

Package 3 height

30 cm

Package 3 width

30 cm

Package 3 length

40 cm

Package 3 weight

11.79 kg
Show all specifications